GDHX-8300F Wireless Phase Detector

GDHX-8300F Wireless Phase Detector

Brief Description:

GDHX-8300F Wireless Phase Detector is mainly used for phase sequence identification and labeling of power transmission and distribution lines.

Its working principle is: the phased base station regularly collects the phase signal of a certain area line as a standard signal and uploads it to the main station server. During measurement, the sensor collects the measured line signal and sends it to the handheld device. The handheld device applies to the server for the data of the phasing base station at the same time. By comparing the two phase data, the true phase of the measured line can be calculated.

The complete set of equipment mainly consists of the main station server, phasing station, handheld machine, sensors and accessories.


Product Detail

Product Tags

Feartures
  • Function: Identify the phase sequence of power transmission and distribution lines.
  • Four functions: Integrated network phasing, network-free phasing, remote phasing, and local phasing.
  • A set of base stations can match an unlimited number of handheld devices to work simultaneously.
  • The system can perform nuclear imaging in places where there is no GPS or Beidou satellite positioning system and mobile network.
  • The phased base station uses a high-protection aluminum box, which is waterproof and dustproof, and can be used outdoors.
  • The phasing base station can automatically sleep according to the system working status to save network traffic.
  • The phasing base station is a full network standard.
  • The handheld machine has vector graphics and text display, which is convenient and intuitive.
  • The handheld device displays detailed information to facilitate data judgment by professionals.
  • The handheld device has an automatic shutdown function. It will automatically shut down after a certain period of inactivity.
Technical Parameter

Item

Specification

Host

Phase difference accuracy

5°

Satellite PPS timing error

50ns

Storage environment

-4055℃,humidity95

operating environment

-2045℃,humidity80

Station

station power supply

AC 100~240V50~60Hz

station signal input

AC 220V50~60Hz

Size

300mm×200mm×100mm

Security

Between housing and power supply   2kV AC1Min

Handheld machine

Display

800×480 bright color LCD display

Battery

18650Lithium battery3.7V6700mAH

Communication distance from sensor

Max. 40 meters

Size

226mm×140mm×55mm

Charger

Shared with sensor

Sensor

Battery

Lithium polymer battery3.7V 500mAH

Input voltage

20V~200kV AC

DC input voltage

Max.500V AC

Current leakage

20uA@Max. direct input voltage

Charger

Input100-240VAC50/60Hz  Output 5V/3A


  • Previous:
  • Next:

  • Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us